Blauberg Axis-QRA 150
- Description
- Characteristics
- Capacity diagram
- Downloads
- Designation key
- Dimensions
- Additional characteristics
USE
Supply and extract ventilation systems installed in various premises. Mounting in ventilation systems with low static pressure requiring high air capacity. Direct air extract. MOTORSingle-phase asynchronous motor with an internal rotor and an axial impeller. Motor with slide bearings. Integrated overheating protection with automatic restart. SPEED CONTROLSmooth speed control with an external thyristor controller or step speed control with an external auto transformer (both available upon separate order). |
DESIGN
Compact steel casing covered with special polymer coating. Aluminium impeller. The casing is equipped with a round mounting plate and flange for easy surface wall mounting. The fan is equipped with a power cord and external terminal box for connection to power mains. MOUNTINGWall surface mounting with a round connecting frame. Horizontal installation with respect to air flow direction in the system. Power supply through an external terminal box with electric lead-in. |
Parameter | Axis-QRA 150 60 Hz |
Axis-QRA 150 50 Hz |
Measurement unit |
---|---|---|---|
Voltage | 220-240 | 220-240 | V |
Phase | 1 | 1 | ˜ |
Frequency | 60 | 50 | Hz |
Current | 0.26 | 0.26 | A |
Power | 26 | 36 | W |
RPM | 1590 | 1300 | min-1 |
Maximum air flow | 57 | 56 | l/s |
Maximum air flow | 205 | 200 | m³/h |
Sound pressure level at 3 m | 33 | 33 | dBА |
Max. operating temperature | -30 … +40 | -30 … +40 | °С |
Motor IP rating | IP44 | IP44 | - |
Ingress protection rating | IPX4 | IPX4 | - |
EC motor | no | no | - |
Weight | 1.91 | 1.91 | kg |
Casing material | polymer-coated steel | polymer-coated steel | - |
Outdoor mounting | no | no | - |
Sound-insulated casing | no | no | - |
Air duct | for round air ducts | for round air ducts | - |
Connection diameter | 150 | 150 | mm |
Design | axial | axial | - |
Type | Exhaust, Supply | Exhaust, Supply | - |
Mounting | wall mounting | wall mounting | - |
- Selection method:
- Air capacity:
- Pressure:
- Air capacity: --
- Pressure: ---
Series | Dimension type |
Axis-QRA | 150: branch pipe ø 162 mm 200: branch pipe ø 208 mm 250: branch pipe ø 262 mm 315: branch pipe ø 312/315 mm |
Model | Overall dimensions [mm] | ||||
Ø D | Ø D1 | Ø D2 | Ø d | L | |
Axis-QRA 150 | 162 | 190 | 220 | 7 | 120 |
Sound power level, A-weighted | Octave frequency bands [Hz] | ||||||||
Total | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
LwA to environment [dBA] | 46 | 47 | 56 | 45 | 35 | 30 | 31 | 31 | 20 |