Blauberg KOMFORT EC DW 2000-2 R


Suspended heat recovery air handling unit. Maximum air flow up to 1950 m³/h.
EAN codeEAN4058448021459
  • Description
  • Characteristics
  • Downloads
  • Designation key
  • Accessories
  • Dimensions
  • Capacity diagram
Description
Description
FEATURES

Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings. Heat recovery minimises ventilation heat losses. Provide controllable air exchange to create the best suitable indoor microclimate. Compatible with round Ø 200 to 400 mm round air ducts.

DESIGN

The casing is made of double-skinned aluzinc panels, internally filled with 20 or 25 mm mineral wool layer for heat and sound insulation. The casing has fixing brackets with vibration absorbing connectors for easy installation. The spigots for connection to the air ducts are located at the side of the unit and are rubber sealed for airtight connection to the air ducts. The service panel ensures easy access to the internals for cleaning, filter replacement and other maintenance operations.

 

FANS

High-efficient external rotor EC motors and centrifugal impellers with backward curved blades are used for air supply and exhaust. EC motors have the best power consumption to air flow ratio and meet the latest demands concerning energy saving and high-efficient ventilation. EC motors are featured with high performance, low noise level and totally controllable speed range. Dynamically balanced impellers.

HEAT RECOVERY

The unit is equipped with a plate counter-flow aluminium heat exchanger for heat recovery. The unit condensate is collected and drained to the drain pan under the heat exchanger. The air flows are completely separated in the heat exchanger. Thus smells and contaminants are not transferred from the extract air to the supply air. Heat recovery is based on heat and/or humidity transfer through the heat exchanger plates. In the cold season supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air. Heat recovery minimizes ventilation heat losses and heating costs respectively. In the warm season the heat exchanger performs reverse and intake air is cooled in the heat exchanger by the cool extract air. That reduces operation load on air conditioners and saves electricity.

FREEZE PROTECTION

The electronic frost protection system based on bypass and heater is used to prevent the heat exchanger freezing in cold seasons. The bypass damper is opened and the heater is turned on automatically according to the feedback from the temperature sensor. Cold intake air passes by the heat exchanger and is warmed up to set temperature in the heat exchanger. Synchronously extract air that passes by the heat exchanger is used for its defrosting. After a freezing danger is over the bypass damper is closed, the heater is turned off. The unit reverts to the normal operation mode.

AIR HEATER

The unit is equipped with a water (glycol) heater for operation at low outside air temperature. The integrated water heater is activated to warm up supply air flow if set indoor air temperature may not be reached by means of heat recovery only. Heat medium temperature control ensures supply air temperature maintaining. The air temperature sensor downstream of the waterheating coils and the return water temperature sensor are used for freezing protection of the water heater.

  AIR FILTRATION

The built-in G4 supply filter and G4 extract filter provide air filtration.

CONTROL AND AUTOMATION

The unit incorporates an integrated control system with a wall-mounted control panel and a sensor display. The standard delivery set includes a 10 m cable for connection of the unit and the control panel. Automation functions:

  • Activating/deactivating the unit.
  • Setting required speed for the supply and extract fan for the unit air flow control. Each speed is individually adjusted during set-up.
  • Set supply air temperature maintaining by means of the circulating pump and heat medium regulating valve control.
  • Water heater freezing protection on feedback from the temperature sensor downstream of the water heating coils and the return water temperature sensor.
  • Pre-heating cycle prior to the heater start and maintaining set return water temperature during the fan shutoff.
  • Opening/closing the bypass damper for summer ventilation.
  • Setting and maintaining room or duct air temperature.
  • Timer activation/deactivation and set-up.
  • Setting day- and week-scheduled operation of the unit.
  • Operation control on feedback from FS1 duct humidity sensor (to be ordered separately) or on the humidity sensor in the control panel.
  • Filter clogging control.
  • System shutdown on signal from the fire alarm panel.
  • Controlling supply and exhaust air dampers (to be ordered separately).
  • Cooler control (to be ordered separately).
MOUNTING

Mounting to the ceiling with fixing brackets. The correct mounted unit must provide free condensate collection and drainage as well as good access for servicing and filter replacement. Servicing access on the bottom.

Characteristics
Characteristics
Parameter KOMFORT EC DW 2000-2 R Measurement unit
Number of water coil rows 2 -
Voltage 230 V
Phase 1 ˜
Frequency 50/60 Hz
Current 5.00 A
Power 840 W
RPM 2920 min-1
Maximum air flow 1950 m³/h
Maximum air flow 542 l/s
Sound pressure level at 3 m 58 dBА
Insulation 25 mm mineral wool mm
Transported air temperature -25…+40 °С
Extract filter G4 -
Supply filter G4 -
Heat recovery efficiency 75 %
EC motor yes -
Heat exchanger type cross-flow -
Heat exchanger material aluminum -
Weight 194 kg
Connected air duct diameter 315 mm
Casing material aluzinc -
SEC class NRVU -
Mounting ceiling mounting -
ErP 2016 -
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
KOMFORT ЕС DW - data sheet (pdf 1.01Mb)
KOMFORT ЕС DW - user manual (pdf 7.69Mb)
KOMFORT ЕС DW - image (png 462.77Kb)
Designation key
Designation key
Series Motor type Mounting type Heater type Rated air flow [m³/h]   Number of water coil rows Service side
KOMFORT EC: electronically commutated motor D: suspended mounting, horizontally directed spigots W: water heater 2000; 3800 2 R: right
Accessories
Accessories
    KOMFORT EC DW 2000-2 R
G4 panel filter FP 708x480x48 G4
Silencer SD 315
Silencer SDF 315
Backdraft air damper VRV 315
Air damper VKA 315
Internal humidity sensor FS1
Electric actuator LF230
Electric actuator TF230
Water mixing unit WMG
Dimensions
Dimensions

Model Overall dimensions [mm]
D B B1 B2 H L L1
KOMFORT EC DW 2000-2 314 950 915 405 761 1400 1453
Capacity diagram
Capacity diagram