Blauberg KOMFORT EC DBE 300-E R S21
Maximum air flow up to 340 m³/h.
- Description
- Characteristics
- Downloads
- Designation key
- Accessories
- Dimensions
- Aerodynamic characteristics
FEATURES
Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings. For controllable mechanical energy saving ventilation systems. Heat recovery minimises ventilation heat losses. Control of air exchange for creating comfortable indoor microclimate. Compatible with round Ø 160, 200, 250, 315, 400 mm air ducts. DESIGNThe casing is made of double-skinned aluzinc panels, internally filled with 20 mm mineral wool layer for heat and sound insulation. The casing has fixing brackets with vibration absorbing connectors for easy installation. The spigots for connection to the air ducts are located at the side of the unit and are rubber sealed for airtight connection to the air ducts. The service panel ensures easy access to the internals for cleaning, filter replacement and other maintenance operations. |
FANS
High-efficient external rotor EC motors and centrifugal impellers with backward curved blades are used for air supply and exhaust. EC motors have the best power consumption to air flow ratio and meet the latest demands concerning energy saving and high-efficient ventilation. EC motors are featured with high performance, low noise level and totally controllable speed range. Dynamically balanced impellers. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
KOMFORT EC DBE... 300/550/900 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
HEAT RECOVERY
The air flows are completely separated in the heat exchanger. Thus smells and contaminants are not transferred from the extract air to the supply air. Heat recovery is based on heat and/or humidity transfer through the heat exchanger plates. In the cold season supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air. Heat recovery minimizes ventilation heat losses and heating costs respectively. In the warm season the heat exchanger performs reverse and intake air is cooled in the heat exchanger by the cool extract air. That reduces operation load on air conditioners and saves electricity. AIR HEATERThe unit is equipped with an electric heater for operation during cold seasons at low outside temperature. The integrated electric heater is activated to warm up supply air flow if set indoor air temperature may not be reached by means of heat recovery only. Smooth heat output control ensures automatic supply air temperature maintaining. Two integrated overheat protection thermostats, one actuated at +60 °C with automatic restart and the other one actuated at +90 °C with manual restart. BYPASSThe units are equipped with a bypass for summer ventilation (room cooling by cool air from outside) and heat exchanger freeze protection. AIR FILTRATIONThe built-in G4 supply filter and G4 extract filter provide air filtration. The F7 supply filter (specially ordered accessory) may be used for efficient supply air filtration. MOUNTINGCeiling mounting with fixing brackets. The correct mounted unit must provide free condensate collection and drainage as well as good access for servicing and filter replacement. Access for servicing and cleaning the filter: from the right or left side panel, depending on the unit modification. |
CONTROL AND AUTOMATION
The units are equipped with an S21 integrated automation system. The remote control panel is not included in the delivery set (available separately). The S21 controller allows integrating the unit into the Smart Home system or BMS (Building Management System). The unit can be controlled by the Blauberg AHU mobile application via Wi-Fi.
AUTOMATION FUNCTIONS
option: function is available when purchasing the appropriate accessory (see the "Accessories" tab). |
Parameter | KOMFORT EC DBE 300-E R S21 | Measurement unit |
---|---|---|
Bypass | yes | - |
Voltage | 230 | V |
Phase | 1 | ˜ |
Frequency | 50/60 | Hz |
Max. power without electric heater | 180 | W |
Max. power of electric heater | 1500 | W |
Max. unit current of electric heater | 6.5 | A |
Max. unit current without electric heater | 1.4 | A |
Max. unit power with electric heater | 1680 | W |
Max. unit current with electric heater | 7.9 | A |
RPM | 3270 | min-1 |
Maximum air flow | 94 | l/s |
Maximum air flow | 340 | m³/h |
Sound pressure level at 3 m | 27 | dBА |
Insulation | 20 mm mineral wool | mm |
Transported air temperature | -25...+40 | °С |
Extract filter | G4 | - |
Supply filter | G4 (Option: F7) | - |
Heat recovery efficiency | 69...87 | % |
Heat exchanger type | - | |
Heat exchanger material | enthalpy | - |
Weight | 44 | kg |
Connected air duct diameter | 160 | mm |
Casing material | aluzinc | - |
Type | Supply and exhaust | - |
SEC class | A | - |
Mounting | ceiling mounting | - |
Series | Motor type | Mounting type | Bypass | Heater type | Rated air flow [m³/h] | Heat exchanger type | Service side | Control | Additional elements | |||||||||
KOMFORT | EC: electronically commutated motor | D: suspended mounting, horizontally directed spigots | B: with a bypass | E: electric heater | 300; 550; 900; 2000; 3000 | – | _: heat recovery E: energy recovery |
L: left R: right |
S21 | _: no additional elements DTV: equipped with a differential pressure switch to control filter contamination |
KOMFORT EC DBE 300-E R S21 | ||
G4 panel filter | FP 440x128x20 G4 | |
G4 pocket filter | FPT 208x236x27 G4 | |
F7 pocket filter | FPT 208x236x27 F7 | |
Control panel | S22 | |
Wireless control panel | S22 Wi-Fi | |
LCD control panel | S25 | |
Humidity sensor | FS2 | |
CO₂ sensor with indication | CD-1 | |
CO₂ sensor | CD-2 | |
Humidity sensor | HR-S | |
VOC sensor | DPWQ30600 | |
CO₂ sensor | DPWQ40200 | |
Humidity sensor | DPWC11200 | |
Kitchen hood | DAH 251-13 | |
Electric preheater | EVH 160 | |
Syphon kit (for the units without an enthalpy heat exchanger) | SFK 20x32 | |
Silencer | SD 160 | |
Backdraft air damper | VRV 160 | |
Air damper | VKA 160 | |
Electric actuator | LF230 | |
Electric actuator | TF230 |
Model | Overall dimensions [mm] | |||||
Ø D | B | B1 | H | L | L1 | |
KOMFORT EC DBE 300-E R S21 | 160 | 485 | 577 | 290 | 1238 | 1291 |
|
Sound power level, A-weighted | Total | Octave frequency band [Hz] | LpA 3 m | LpA 1 m | |||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to supply inlet [dBA] | 66 | 13 | 51 | 65 | 54 | 51 | 47 | 37 | 28 | ||
LwA to supply outlet [dBA] | 75 | 14 | 53 | 68 | 65 | 67 | 69 | 64 | 64 | ||
LwA to exhaust inlet [dBA] | 62 | 11 | 45 | 61 | 52 | 51 | 48 | 38 | 34 | ||
LwA to exhaust outlet [dBA] | 71 | 12 | 47 | 62 | 66 | 61 | 64 | 55 | 61 | ||
LwA to environment [dBA] | 48 | 17 | 30 | 43 | 45 | 36 | 35 | 31 | 35 | 27 | 37 |
Data provided for point 1 of the air flow diagram